5.4. MultiSensor-LAN
In contrast to the MultiSensor-RF with radio interface the MultiSensor-LAN can also be used stand-alone
without an AlarmManager. For configuration in stand-alone operation a web server is integrated, which
allows you to configure the device via LAN and a web browser. With the SNMP interface, an integration in
network management systems is possible.
Connection via PC: Connect the LAN jack of the MultiSensor-LAN with your network and your PC#
using a LAN cable. Please note that you have to use a Cross-Over network cable for
a direct connection. Set the IP address of your PC to e.g. „192.168.100.123“.
5.4.1. Default settings / Factory defaults
Voltage supply: PoE (Power over Ethernet). Change to external power supply possible.
Default IP-address: 192.168.100.223
Subnet mask: 255.255.255.0
User: admin
Password: password
5.4.2. Kentix system jack - MultiSensor-LAN
Via the Kentix system jack, located in the front of the MultiSensor-LAN, system components such as leakage
detectors, door contacts, acoustic signals or alarms of USPs or climate devices can be connected. The
MultiSensor-LAN is powered via the Kentix system jack.
To connect external devices or alarm in- or outputs, two connector modules are available:
1) Power-Adapter KIO 1: Power supply, 2 digital inputs
2) Power-Adapter KIO 2: Only power supply
3) Power-Adapter KIO 3: Power supply, 2 digital inputs and 2 relay outputs
5.4.3. Software function MultiSensor-LAN
In the following, the stand-alone functionality of the integrated web server is described. For the described
functionality no AlarmManager is required. When operating the MultiSensor-LAN with the AlarmManager-
PRO, the AlarmManager controls the configuration and monitoring functions.
1 - Internal system voltage (GND)
2 - Alarm output 1 (Open Collector 100mA)
3 - Alarm output 2 (Open Collector 100mA)
4 - Power supply 10-32VDC (+/-)
5 - Power supply 10-32VDC (+/-)
6 - Alarm input 1 (External dry contact, no/nc)
7 - Alarm input 2 (External dry contact, no/nc)
8 - Internal system voltage (5V)
Important! Reset to factory defaults
If you forgot IP-address or the login information of the MultiSensor-LAN, press the RESET button at the
back of the sensor. The device will reset to factory defaults and reboot. After 30 seconds the MultiSensor
can be accessed with the default IP-address and default user data.