8.2. Kentix Power-Adapter (KIO1) with digital input clips
The Kentix I/O Power-Adapter is used to expand your Kentix-solution to include the additional functions:
• Power supply for up to two MultiSensors-RF via an AC adapter
• Connecting of up to two external alarms via dry contacts to a MultiSensor
#
The adapter is connected directly to the Kentix system jack and offers the possibility to power the
MultiSensor with a power plug or a permanently connected AC adapter.
The cable length between MultiSensor and the KIO1 adapter should not exceed the following lengths:
• Power supply only: up to 50m
• Power supply with digital inputs: up to 10m
Figure 1: Back of Kentix Power-Adapter (KIO1)
Figure 2: Circuit diagram
"
Important!
When using the input clips for external alarms and simultaneous power supply of two MultiSensors remove
the jumpers. Otherwise the external alarms will be indicated on both sensors.