EnergySensor - Energy
Shows all actual energy measurement values for PDU 1+2 (PDU=Power Distribution Unit), the energy
consumption with costs and the alarm state in one table.
Voltage
Display of the actual mains voltage in volt (V).
Flicker
Display of voltage drops of the supply voltage over a configured period of time (number of half-waves,
minimum 1 half-wave) for each PDU as time value / time. Always the last appearance of a voltage drop will
be displayed.
Swell
Display of voltage overshoots of the supply voltage over a configured period of time (number of half-waves)
for each PDU as time value / time. Always the last appearance of a voltage drop will be displayed.
Peak
The MultiSensor-RACK measures the supply voltage with a sampling rate of 4000 measurements / second
(250 µs per measure). A peak is the highest value per second.
Overshoots of the line voltages configured tolerance range in volt with the time of the appearance are
displayed in the table (last appearance of a peak).
Current
Display of the actual power demand of the connected power consumers in ampere (A).
Frequency
Actual mains frequency in hertz (Hz).
The frequency determines the length of the half-waves (50 Hz ≙ 10 ms, 60 Hz ≙ 8,33 ms).